Condenser water flow calculator

How many litres of water per minute the condenser needs at a given heating power – and how much water the whole run uses.

Calculate the minimum water flow needed by a condenser or dephlegmator at a given heating power, plus total water consumption and cost during distillation.

Enter your data

W
For the product condenser ≈ heater power.
°C
°C
h
zł/m³
Example: At 2.5 kW and water warming from 12°C to 40°C the condenser needs about 1.3 l/min, i.e. about 77 litres per hour.

How much water does a condenser need?

All the heater energy that turns into vapour must be removed in the condenser. Water absorbs 4.19 kJ per kilogram per degree, so the more you let it warm up, the less of it you use.

Saving water

Set the flow so the outlet water is warm but the distillate comes out cool. A needle valve is best for precise control of small flows. A closed loop with a pump, reservoir and air cooler saves even more.

How we calculate

Mass flow ṁ = P / (c × ΔT), where c = 4186 J/kg·K. For water 1 kg ≈ 1 l, so flow in l/min = P / (4186 × ΔT) × 60.

Frequently asked questions

How can I save water when distilling?

Set a higher outlet water temperature (e.g. 40–50°C), use a needle valve for precise control, or a closed loop with a pump and reservoir.

How do I descale a condenser?

Fill the condenser jacket with a citric acid solution (about 50 g per litre of warm water), leave for an hour and rinse thoroughly. Scale acts as an insulator and reduces cooling performance.

Can I cool with a closed loop?

Yes. You need a pump, a water tank (at least 50–100 l) and ideally an air cooler with a fan. The water in the loop gradually warms up, so the tank must be large enough.

What should the condenser outlet water temperature be?

For a product condenser usually 30–45°C. Water warmer than about 55°C risks under-cooling the distillate and losing alcohol vapour.